Spesifikasi

 

Baterai
  • Battery Type : 12V/ 9 AH
  • Numbers : 6
  • Typical Recharge Time : 3 hours recover to 95% capacity for internal battery @2A charging current
  • Charging Current : default 2A, max. 8A adjustable; 200/208/220/230/240/ VAC models: default 2A, max. 12A adjustable
  • Charging Voltage : 82.2VDC ± 1%
Daya Keluar 3000VA/3000W
Form Factor Tower
Lain-lain
  • 1 PHASE IN / 1 PHASE OUT
  • LCD Panel : Load level, Battery Level, AC Mode, Battery Mode, Bypass Mode, and Fault Indicator
  • Alarm : Battery Mode Sounding every 5 second; Low battery Sounding every 2 second; Overload Sounding every second; Fault Continously sounding
  • Humidity : 20-95 % RH @ 0- 45°C (non-condensing)
  • Noise Level : Less than 50dBA @ 1 Meter with Fan speed control
  • Efficiency : Line Mode ≥91% @ battery fully charged; ECO Mode ≥96% @ battery fully charged; Battery Mode ≥90%
Dimensi Produk 421 x 190 x 318mm
Voltase Masuk
  • INPUT Nominal Voltage : 100/110/115/120/127 VAC or 200/208/220/230/240
  • Voltage Range : 55 – 150 VAC ± 3% or 110 – 300 VAC ± 3% at 50% load; 80 – 150 VAC ± 3% or 160 – 300 VAC ± 3% at 100% load
  • Frequency Range : 40Hz ~ 70Hz
  • Power Factor : ≥ 0.99 @ nominal voltage (100 load)
  • THDi% : ≤ 5%
Voltase Keluar
  • Output Voltage : 100*/110*/115*/120*/127* VAC or 200*/208*/220*/230*/240 VAC
  • AC Voltage Regulation (Batt. Mode) : ± 1 %
  • Frequency Range (Synchronized Range) : 47 ~ 53 Hz or 57 ~ 63Hz
  • Frequency Range (Batt. Mode) : 50Hz ± 0.1Hz or 60Hz ± 0.1Hz
  • Current Crest Ratio : 3 : 1
  • Harmonic Distortion : ≤2% THD (Linear Load), ≤4% THD (Non-linear Load)
  • Transfer Time AC to DC : Zero; Inverter to Bypass : 4 ms (Typical); ECO to Battery Mode : 8 ms (Typical), 10 ms (max)
  • Waveform (Batt. Mode) : Pure Sinewave
Antarmuka / Interface
  • Modbus RS-232 or USB : Supports Windows ® 2000/2003/XP/Vista/2008, Windows ® 7/8/10, Linux and MAC
  • Optional SNMP : Power management from SNMP manager and web browser

Produk lain UPS

Rp (Hubungi CS)
Rp (Hubungi CS)
Rp (Hubungi CS)
Rp (Hubungi CS)
Rp (Hubungi CS)

Alamat Kami

Jln. Jemur Andayani No 50
Ruku Surya Inti Permata
Blok D 86/87 Lantai 1
Email : marketing@agcsmart.com / agcsmart002@yahoo.com
Telephone Hotline :
031 8474486 / 87
0822 3168 3554 0822 5766 5632 (Telkomsel)

Buka Senin-Sabtu Jam 08.30-16.30 Wib. Hari Minggu/Merah Tutup

Teknisi Komputer

Email Teknisi : cs.ptanriz@gmail.com

Pengiriman

Rekening Bank

031 847 4487

082257665632
sales@anriz.co.id